Customization: | Available |
---|---|
Certification: | ISO, CE |
Power Supply: | AC DC24V AC230V |
Still deciding? Get samples of US$ 750/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model Para. |
ExS6061SF-05DF/24V |
ExS6061SF-05DF/230V |
ExS6061SF-10DF/24V |
ExS6061SF-10DF/230V |
ExS6061SF-15DF/24V |
ExS6061SF-15DF/ 230V |
|
Torque |
5Nm |
10Nm |
15Nm |
||||
Damper Size |
1m2 |
3m2 |
4.5m2 |
||||
Power Supply |
AC220V AC24V DC24V 50/60Hz i ≤0.2A AC220V 50/60Hz |
||||||
Consumption |
7W run/3W remain |
10W run/3W remain |
12W run/3W remain |
||||
Wire Size |
10VA |
||||||
Connection cable |
Power:1m cable 3*0.5 m2 |
||||||
Auxiliary Switch (F):1m cable 6*0.5 m2 |
|||||||
Running Time |
Motor≤150s;Spring Return≤30s |
||||||
Angle of Rotation |
Max 93º |
||||||
Position Indication |
Mechanical indicator |
||||||
Weight |
5Kg |
||||||
Life Cycle |
≥10000 cycles |
||||||
Sound Level |
50dB(A)and62dB(A) |
||||||
IP Protection |
IP66 |
||||||
Ambient Temperature |
-20~+60ºC |
||||||
Ambient Humidity |
5~95%RH |
||||||
Explosion-proof Mark |
Ex db B T6 Gb Ex tb IIIC T85°C Db |
Single control
Form-fit 12x12cm shaft
Universal shift plug
Two auxiliary switches
Cast aluminum housing, compacting type
Safety meets IP66
IEC60079-0:2017, EN60079-0:2012+A11:2013 electrical apparatus in explosive gas atmosphere - part0: General requirements.
IEC60079-1:2014 ;EN60079-1:2007 electrical apparatus in explosive gas atmosphere - part1:flameproof"d".
IEC60079-31:2013,EN60079-31:2014 explosive atmospheres part31: Equipment dust ignition protection by enclosure "t". Usage and maintenance
Cable connector and the housing mating thread size M16 × 1.5, cable diameter size Φ6-Φ8. When the equipment is used on-site, the cable gland should be installed by the user, whose protection grade should not be lower than 2D Ex tb IIIC T85°C Db.
Within ground terminal tightening torque 2N.m.
Flameproof joint tightening torque is 3.2N.m.
External ground bolt M4X6, pressing 4mm² conductors.
Disassembly is prohibited without permission Do not open with power. please do not open the cover in the explosive gas. Need to use a damp cloth when opening.l
Repair of the flanged joints must be made in compliance with the structural specifications provided by the manufacturer. Repairs must not be made on the basis of values specified in table 3 and table 4 of EN 60079-1:2007.
The entry shall be equipped with Ex certified cable glands with a compatible mode of protection for the intended use.
When assembly, operation and maintenance, the operator should follow the requirements of EN 60079-14, besides the instruction manual.
Repair and overhaul shall comply with EN 60079-19.