24nm Modulating Electric Motor for HVAC System Damper Actuator

Product Details
Customization: Available
Certification: ISO, CE
Power Supply: AC DC24V AC230V
Still deciding? Get samples of US$ 40/Piece
Request Sample
Manufacturer/Factory & Trading Company
Gold Member Since 2021

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

to see all verified strength labels (31)
Find Similar Products

Basic Info.

Power Source
Electric Power
Temperature
Ordinary Temperature
Connection
Thread
Material
Stainless Steel
Transport Package
Cartons
Trademark
SOLOON
Origin
China
Production Capacity
10000 Per Month

Product Description

 

Features of S6061-08~24 Standard Damper Actuator (Non Fail-Safe Damper Actuators)

 

  • Torque 08-16-24NM

  • 2 or 3 points control or Modulating

  • Actuator and damper shaft are bolt-on by screw.

  • Maximum round shaft φ16 and square shaft 12*12mm.

  • Direction of rotation can be setting.

  • Manual Override

  • With 2 auxiliary switches are optional

  • Power supply AC/DC 24V or AC 230V

 

 

 

Technical datasheet of S6061-08~24 Standard Damper Actuator (Non Fail-Safe Damper Actuators)

 

Item

Unit

S6061-08DN(F)

S6061-16DN(F)

S6061-24DN/(F)

Torque

Nm

8

16

24

Damper area

m2

2

4

6

Running time

sec

30~40

72~88

117~143

Power supply

V

24VAC/DC;220VAC;110VAC

Frequency

Hz

50/60Hz

7.5W 50/60Hz

Running consumption

W

3.9W(24V);4.8W(230V)

Maintaining consumption

W

0.4W(24V);1.2W(230V)

Weight

Kg

1.25

Control signal

2/3 point

Position signal

2 auxiliary switches

Rotation angle

0~90º(max 93°)

Limited angle

5~85º(per step 5º)

Auxiliary switch rating

3(1.5)Amp 250V

Life cycle

>70000 cycles

Noise level

45dB(A)

Protection level

IP44 or IP54

Ambient Temperature

-20~+50ºC

Ambient Humidity

5~95%RH

Storage temperature

-40~+70ºC

Certification

CE UL(Except 230V)

 

 

Wiring diagram of S6061-08~24 Standard Damper Actuator (Non Fail-Safe Damper Actuators)

 

The damper actuator can be controlled by 2 or 3 point.

24nm Modulating Electric Motor for HVAC System Damper Actuator

Auxiliary switch of S6061-08~24 Standard Damper Actuator (Non Fail-Safe Damper Actuators)

There are 2 auxiliary switches of the actuator, and you can set the angle 0-90° (the factory sets a is 10° and b is 80°). It will output a on/off signal when the actuator rotates the setting angle.

 

24nm Modulating Electric Motor for HVAC System Damper Actuator

 

Control signal and choose the direction of rotation of S6061-08~24 Standard Damper Actuator (Non Fail-Safe Damper Actuators)

The direction of rotation changes according to the direction of pin.

24nm Modulating Electric Motor for HVAC System Damper Actuator

 

 

Outline and dimension of S6061-08~24 Standard Damper Actuator (Non Fail-Safe Damper Actuators)

 

24nm Modulating Electric Motor for HVAC System Damper Actuator

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now